Multiply the wire’s original 90°C ampacity (30A for 12 AWG) by 0.71:
At 55°C ambient, the factor is .
Without derating, that 16-amp load would push conductor temperature over the limit. Insulation hardens, cracks, and eventually shorts. Alex opens the NEC (National Electrical Code) Table 310.16 — the standard wire derating chart. It tells him: wire derating chart
1. The Setup: A Perfectly Rated Circuit An electrician named Alex finishes wiring a new commercial kitchen. He runs a 12 AWG copper wire — rated for 20 amps at room temperature — from the breaker panel to a dedicated outlet for a large mixer. By the book, 12 AWG + 20A breaker = safe, legal, functional. Multiply the wire’s original 90°C ampacity (30A for
However, if the mixer draws 16A continuously (more than 3 hours), the wire must be derated again by 125% — but here, 16A is fine. But Alex realizes: — because the breaker is thermal and also affected by ambient heat. 4. The Multiplier Trap Alex also has four current-carrying conductors in the same conduit (not just two). Table 310.15(C)(1) says: 4–6 conductors → derate by 0.80. Alex opens the NEC (National Electrical Code) Table 310